FRP for Automotive and Surface Treatment

Automotive plants use FRP where the process is wet chemistry: plating, phosphating, anodizing, pickling, e-coat pretreatment and the effluent treatment that follows all of them.

Hot baths are harder than cold chemicals

A surface treatment line is a row of tanks holding aggressive chemistry at temperature, and the temperature is what makes it difficult.

Chemical resistance falls as temperature rises. A phosphating bath at 50 °C and the same chemistry at 20 °C are different design problems, and the resin that suits one may not suit the other.

The bath list is familiar and each entry changes the answer:

  • Sulphuric, hydrochloric and phosphoric acid — pickling and phosphating.
  • Chromic acid and chromate solutions — strongly oxidising, which narrows the resin choice sharply.
  • Caustic and alkaline cleaners, usually hot.
  • Nickel, zinc and copper plating solutions.
  • Rinse water, which is the mild one — until you notice it carries drag-out from every bath before it.

Send the bath chemistry with its operating temperature. Without the temperature, the chemistry alone is not enough to choose a resin.

The duct usually fails before the tank

The tanks get the attention. The ductwork above the line does the harder job.

Fume extraction over hot acid baths handles a gas stream that is warm, wet, and condensing — and condensing acid is far more aggressive than the same acid in the bath below it. The duct is also usually on the suction side of a fan, which means it sees vacuum, and vacuum collapses ducts.

Two numbers to send for the extraction system:

  • The condensate, meaning which acid the vapour condenses as, and at what temperature the duct surfaces sit.
  • The maximum vacuum, including with filters loaded or a damper closed — not the figure on a good day.

Typical equipment

Process and rinse tanks for plating and pretreatment lines, fume extraction ducting, scrubbers for acid and alkaline fume, effluent and wastewater treatment tanks, chemical storage and dosing, and grating and walkways along the line where drag-out and spillage kill steel.

What to send us

  • Each bath: chemistry, concentration and operating temperature.
  • Tank dimensions, or the line layout if it is being replaced.
  • Whether the tanks are heated, and how — immersion heaters and coils are a local load and a local hot spot.
  • The extraction system: airflow, condensate chemistry, and maximum vacuum.
  • Site location, for seismic and wind loading.

Contact a sales engineer

Choose your preferred contact method

Posted on • by PITSA FRP